11 May, 2024

Ten key steps to enhance pressure relief system efficiency

24 January, 2024

Clint Botard, Programme Manager of the Asset Integrity Management Services business at ABS Consulting, highlights ten essential steps to optimise pressure relief system efficiency while maintaining regulatory compliance.


Process Safety Management (PSM) that covers industrial facilities are required to manage risk and regulatory compliance for pressure-relief systems (PRSs) and pressure-relieving devices (PRDs).

PRDs are an important line of defence in your facility and a key barrier preventing overpressure events from developing into catastrophic failures. Errors in the design, installation, or maintenance of a PRS, whether sizing, rationale, installation or others, often result in loss of containment, human injury, equipment damage and catastrophic process safety events.

Below are ten essential steps to optimise pressure relief system efficiency while maintaining regulatory compliance. These steps can be divided into 3 phases: Data Validation, Scenario ID & Analysis, and Inspection and Testing.

Data Validation

The initial equipment validation phase contains the first three key steps. The collective goal of these steps is to evaluate the system boundaries and equipment, also comparing its current performance to its intended performance:

Step 1: Develop a master asset list

A master asset list details all relief devices and relief systems covered by the Mechanical Integrity (MI) programme. MI is among the 14 elements in the PSM standard, OSHA 1910.119. The requirements of the MI programme include management responsibility, equipment selection and the execution of testing and maintenance strategies. Appropriately trained and certified personnel are a vital part of the MI programme and, therefore, a crucial part of this step.

Step 2: Validate the as-built condition

The as-built condition of each relief device listed on the master asset list is validated by performing field walk-downs in the facility to ensure that relief device information is accurate. Typical tasks performed during field walk-downs include photographing the device and ID tags and creating isometric sketches of each device or system.

Step 3: Ensure references for each device

All devices and systems need documented process safety information and references to Recognised and Generally Accepted Good Engineering Practices (RAGAGEPs).

Scenario ID and analysis

This phase involves reviewing the PRD design and anticipated operating conditions. An experienced engineering team will review and document credible and non-credible overpressure scenarios to determine the device’s ability to perform as intended.

Step 4: Review credible overpressure scenarios

After ensuring that all equipment has been documented and validated, the engineering team will begin reviewing the different scenarios to determine the governing scenario. Ultimately, the sizing and relief load calculations will be based on this information.

Step 5: Perform sizing and relief load calculations

Once the governing scenario has been determined, each device or system will need to be analysed based on the governing overpressure scenario. If the device is projected to have issues functioning like it should in that circumstance, the existing calculations will need to be updated based on that new information. Process stream properties will be reviewed and defined during this step.

Step 6: Determine if additional analysis is required

As a final step in the design review and preparation phase, the engineering team will determine if additional analysis is required for the system. Examples of additional analysis include process stream flow rate and seeing if the pressure drop is sufficient to cause acoustic-induced vibration (AIV), flow-induced vibration (FIV), excessive loading on inlet and outlet piping during discharge, dispersion modelling, or runaway chemical reactions. Any steps necessary to remedy these additional issues should be performed during this step.

Step 7: Use calculations to determine adequate relief device specifications

Pressure relieving devices include mechanisms such as Pressure Safety Valves (PSV) and Pressure Relief Valves (PRV). However, there are other types of pressure-relieving devices as well, such as Rupture Disk Devices and Pin-Actuated Devices. If designed, installed and maintained correctly, these different devices will have the correct capacity for allowing anticipated pressurised fluids or gases to enter and escape so that pressure cannot build up beyond safe operating limits. Upon completion of calculations, an engineer will be able to specify and procure the correct PRV (i.e., type, code, basis, service, body, trim, manufacturer, serial no, etc.) for the requirements. Inspection and testing This final phase of ensuring optimal pressure relief system efficiency involves the design and execution of an appropriate inspection and testing programme while the device remains in the field (in service or out of service).

Step 8: Develop an ITP for each device

An inspection testing plan (ITP) helps to maintain the safety, efficiency, and effectiveness of each device. Once set, this information can be entered into the inspection database management system (IDMS) or whatever database the organisation uses.

Step 9: Perform inspection and testing

Once an ITP has been developed for each device and entered into the data management system, inspection and testing can take place following the guidelines set forth in API RP 576.

Step 10: Evergreening

A good evergreening programme will have a complimentary workflow that helps staff to identify, align, develop and execute change in a structured approach which helps a facility to protect its original investment, reduce verification burdens and not repeat expensive revalidations every 5 to 10 years.

After PRVs have been analysed, implemented and maintained in the field in “as built” status, facilities should consider implementing an evergreening workflow and strategy.

Changes that are not managed through a rigorous Management of Change (MoC) programme may result in the need to review overpressure scenarios for potential impacts. Additionally, the global flare/vent/scrubber capacity may have changed resulting in inadequate pressure relief capacity.

In these cases, revalidation of PRSs or specific PRDs may be required when process safety information (PSI) is missing/inadequate or when process or organisational changes occur that impact PRS or PRD requirements.

Conclusion

Managing PRVs is complex, challenging and often misunderstood. Implementing these 10 steps will help you to optimise your PSV programme and help it operate on solid ground.

For further information please visit: https://www.abs-group.com

https://twitter.com/_absgroup

https://www.linkedin.com/company/absgroup/




Related stories
Events
 
Buyers' Guide Search
 
Search for UK supplier by name
Browse by Product Group.
Magazine
MARCH 2024To view a digital copy of the MARCH 2024 edition of Hydraulics & Pneumatics Magazine, click here.

For a FREE subscription please click here

To visit the Library for past issues click here

JANUARY/FEBRUARY 2024 IssueTo view a digital copy of the JANUARY/FEBRUARY 2024 edition of Hydraulics & Pneumatics Magazine, click here.

For a FREE subscription please click here

To visit the Library for past issues click here

JULY/AUG 2023 Issue inc. BUYERS' GUIDETo view a digital copy of the JULY/AUGUST ISSUE of Hydraulics & Pneumatics magazine that includes the ANNUAL BUYERS' Guide for 2023, click here.

To visit the Library for past issues click here

BFPA YearbookTo read the latest BFPA Yearbook, click here ..
BFPA Training AcademyClick the image to go to the BFPA Training Academy website
Compressed Air & Vacuum Technology Guide 2018To read the official BCAS Compressed Air & Vacuum Technology Guide 2018 click here
Offshore Europe Journal
Newsletter
 
Newsletter